| Status: | Unknown |
|---|---|
| Series: | - |
| RoHS: | Unknown |
| Memory Capacity: Memory Selection Pattern 1 | Program (steps): 121,500 Data register (Note 1): 131,072 Number of max. program block (PB): 243 (Note) The factory default setting is pattern 1. (Note 1) For data register (DT), data up to 262,144 words can be backed up. |
|---|---|
| Memory Capacity: Memory Selection Pattern 2 | Program (steps): 96,000 Data register (Note) : 262,144 Number of max. program block (PB): 192 (Note) For data register (DT), data up to 262,144 words can be backed up. |
| Memory Capacity: Memory Selection Pattern 3 | Program (steps): 64,000 Data register (Note) : 425,984 Number of max. program block (PB): 128 (Note) For data register (DT), data up to 262,144 words can be backed up. |
| Memory Capacity: Memory Selection Pattern 4 | Program (steps): 32,000 Data register (Note) : 589,824 Number of max. program block (PB): 64 (Note) For data register (DT), data up to 262,144 words can be backed up. |
| Programming Method | Relay symbol method |
| Method | Cyclic operation method |
| Program Memory | Built-in flash ROM (no backup battery required) |
| Operation Speed | Basic instruction: min. 11 ns/step |
| External Input (X) | 8,192 points (Note) Hardware configuration governs the actually usable number of I/O points. When I/O points are not actually used, usable as internal relays. |
| External Output (Y) | 8,192 points (Note) Hardware configuration governs the actually usable number of I/O points. When I/O points are not actually used, usable as internal relays. |
| Internal Relay (R) | 32,768 points |
| System Relay (SR) | Indicate operation status of various relays is shown. |
| Link Relay (L) | 16,384 points |
| Timer (T) | 4,096 points: Timer capable of counting (units: 10 micro s, 1 ms, 10 ms, 100 ms or 1 sec.) x 4,294,967,295 |
| Counter (C) (C) | 1,024 points, Counter capable of counting 1 to 4,294,967,295 |
| Link Data Register (LD) | 16,384 words |
| System Data Register (SD) | Internal operation status of various registers is shown. |
| Index Register (I0 to IE) | 15 long words / With switching function |
| Master Control Relay (MCR) | Unlimited |
| Number of Labels (LOOP) | Max. 65,535 points for each program block (PB) |
| Differential Points | Unlimited |
| Number of Step Ladders | Unlimited |
| Number of Subroutines | Max. 65,535 points for each program block (PB) |
| Number of Interrupt Program | 1 periodical interrupt program |
| SD Memory Card Function | SDHC memory cards of up to 32 GB are usable. |
| Real Time Clock | Year (last two digits), month, day, hours (24-hour display) minutes, seconds, day of week (Note)Precision of calendar; At 0 ℃ +32 ℉ , 95 sec. or less error per month, at +25 ℃ +77 ℉ , 15 sec. or less error per month, at +55 ℃ +131 ℉ , 130 sec. or less error per month |
| Battery Life (Value Applies When No Power Is Supplied At All.) | 3.3 years or more (when no power is supplied) actual usage value: 20 years approx. (at 25 degrees 77 degrees Fahrenheit ) |
| Safety Function | Password / Restricted distribution / Read disable setting / Encryption |
| PLC Link Function | Max. 16 units, link relays: 1,024 points, link registers: 128 words. (Data transfer and remote programming are not supported) (Link area allocation is switchable between the first and the second half) |
| Interface | RS-232C, three-wire system, 1 channel (Note) SD, RD and SG terminals are isolated from internal circuits. |
| Transmission Distance | 15 m 49.213 ft |
| Transmission Speed | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 230400 bits/sec, |
| Communication Method | Half-duplex system |
| Synchronous Method | Start-stop synchronization system |
| Transmission Format | Stop bit: 1 bit / 2 bits Parity: none / odd / even Data length: 7 bits / 8 bits Start code: with STX / without STX End code: CR / CR + LF / none / ETX |
| Data Transmission Order | Transmit from bit 0 in character units. |
| :5V | For 5 V DC type GT series Programmable Display (Note) 5 V and 24 V DC types are not usable at the same time. |
| :24V | For 24 V DC type GT series Programmable Display (Note 1) 5 V and 24 V DC types are not usable at the same time. (Note 2) Use 21.6 to 26.4 V DC to power the CPU unit. Please check the “GT Series Hardware Manual” for grounding of the GT series programmable display. |
| Communication Interface | Ethernet 100BASE-TX / 10BASE-TX |
| Communication Speed | 100 Mbps, 10 Mbps auto negotiation function |
| Ber Of Nodes | Max. 254 units |
| Total Cable Length | 100 m 328 ft (500 m 1,640 ft when a repeater is used) |
| Ber Of Simultaneous Connections | Max. 220 connections (user connection: 216, system connection: 4) |
| Communication Protocol (Communication Layer) | TCP / IP, UDP |
| DNS | Supports name servers |
| DHCP/DHCPV6 | Automatic IP address acquisition |
| FTP Server/Client (SSL Compatible) | Server function, file transfer, number of user: 3 Client function, data and file transfer |
| HTTP Server/Client (SSL Compatible) | Server function, system web, Customer web (8 MB), number of concurrent session: 16 Client function, data transfer |
| SMTP Client (SSL Compatible) | Client function, mail transfer |
| SNTP | Time adjustment function |
| General-Purpose Communication | 16 kB / 1 connection (user connection: 1 to 16) |
| Dedicated Communication | Slave communication (MEWTOCOL-COM, MEWTOCOL7-COM, MEWTOCOL-DAT, MODBUS-TCP, MC protocol (Note)) Master communication (MEWTOCOL-COM, MEWTOCOL-DAT, MODBUS-TCP, MC protocol (Note)) (Note): MC protocol is a short form denoting MELSEC communication protocol; MELSEC is a registered trademark of Mitsubishi Electric Corporation. QnA compatible 3E frame, only binary (bulk writing and bulk reading) use is available. |
| Ambient Temperature | 0 to +55 ℃ +32 to +131 ℉ , Storage: -40 to +70 ℃ -40 to +158 ℉ |
| Ambient Humidity | 10 to 95 % RH (at +25 ℃ +77 ℉ , no condensation), Storage: 10 to 95 % RH (at +25 ℃ +77 ℉ , no condensation) |
| Breakdown Voltage | 500 V AC for 1 minute |
| Insulation Resistance | 100 MOhm or more (at 500 V DC) |
| Vibration Resistance | 5 to 8.4 Hz, single amplitude of 3.5 mm 0.138 in , 1 sweep/min. (IEC 61131-2) ; 8.4 to 150 Hz, constant acceleration of 9.8 m/s2, 1 sweep/min. (IEC 61131-2), 10 times each in X, Y, and Z directions |
| Noise Immunity | 1,000 V [p-p] with pulse width 50 ns and 1 micro s (using a noise simulator) |
| Shock Resistance | 147 m/s2 or more , 3 times each in X, Y, and Z directions (IEC61131-2) |
| Operating Condition | Free from corrosive gasses and excessive dust |
| Rated Voltage Range | 20.4 to 28.8 V DC |
| Current Consumption | 200 mA or less |
| Net Weight | 220 g approx. (with terminal block and end unit) |
Where can I find additional details, specifications and documents for a AFP7CPS31ES?
Additional datasheets, footprints and schematics for AFP7CPS31ES are listed on our Part Details page. You can also find images and similar parts to AFP7CPS31ES on this page.
What pricing and inventory information can I view?
Distributor pricing and stock information is available for AFP7CPS31ES on our Product Comparison page. Access via the 'View Pricing & Stock' button to view AFP7CPS31ES price breaks, MOQs, lead times, inventory and SKUs from distributors.
What category does AFP7CPS31ES fall under?
The AFP7CPS31ES is listed under Industrial Automation > PLC & HMI > Programmable Logic Controllers / Interface Terminal > FP7.
Can I view similar or alternative parts?
You can view similar parts to AFP7CPS31ES when available in the FP7 range under the specifications section at the bottom of the details page.
Who can I contact for technical support of the product?
Submit any questions directly to the customer support team of the distributor listing the product. For the AFP7CPS31ES you can contact the distributor directly for product support, shipping queries etc.
Is the AFP7CPS31ES RoHS compliant?
This part has not been flagged as RoHS Compliant.
Which authorised distributors for AFP7CPS31ES have stock available?
Authorised distributors including Ozdisan have stock available or on a lead time for AFP7CPS31ES.
How do I check stock and lead times for all distributors?
Stock availability and lead times will be displayed for AFP7CPS31ES often in real-time on the comparison pages.
What if I can't find stock of AFP7CPS31ES?
You can fill out our help required form which you can use to request a quote for AFP7CPS31ES from some of our verified obsolescence suppliers. Alternatively, contact us via our web chat in the bottom left of your screen and one of our team will try to help.